Article Overview

The thickness of the ground wire (equipment grounding conductor) in a secondary distribution box is determined by the rating of the overcurrent protection device, typically following NEC Table 250.122.

Equipment Grounding Conductor (EGC) Sizing

The equipment grounding conductor (EGC) is the wire that runs with your circuit conductors to provide a low-impedance path for fault current, ensuring that breakers trip quickly during a fault. Its size is based on the rating of the upstream breaker or fuse protecting the circuit, not the continuous load current . For copper conductors, typical minimum sizes according to NEC Table 250.122 are:

  • 15–20 A breaker: 14–12 AWG
  • 30–60 A breaker: 10 AWG
  • 100 A breaker: 8 AWG
  • 200 A breaker: 6 AWG
  • 300 A breaker: 4 AWG
  • 400 A breaker: 3 AWG
  • 500 A breaker: 2 AWG
  • 600 A breaker: 1 AWG
  • 800 A breaker: 1/0 AWG
  • 1000 A breaker: 2/0 AWG For aluminum conductors, the size is generally two gauge sizes larger than copper for the same breaker rating .

Special Considerations for Transformer Secondary

If the ground wire runs between a transformer secondary and the panel, it may be considered a supply side bonding jumper (SSBJ) rather than a standard EGC. In this case, NEC Table 250.102(C)(1) applies, and the size may differ from the EGC table. For example, a 400 A main breaker on a transformer secondary may require a #3 AWG copper EGC to the panel, while the SSBJ could be sized at 1/0 AWG depending on the transformer and system configuration . It is important to distinguish between:

  • EGC: Runs with circuit conductors to the panel, sized by breaker rating (Table 250.122).
  • SSBJ: Connects transformer secondary neutral to ground at the first panel, sized by Table 250.102(C)(1).
  • Grounding Electrode Conductor (GEC): Runs from the panel to the earth, sized by Table 250.66 based on the secondary conductor size .

Summary

  • For a standard secondary distribution box, the ground wire thickness is determined by the breaker rating using NEC Table 250.122.
  • For transformer secondary connections, check if the wire is a supply side bonding jumper; if so, use Table 250.102(C)(1).
  • Always verify whether the conductor is copper or aluminum, as aluminum requires a larger gauge.
  • Proper sizing ensures safety, code compliance, and reliable fault clearing. By following these NEC tables and guidelines, you can select the correct ground wire thickness for your secondary distribution box installation.

DUKE UNIVERSITY CONSTRUCTION STANDARDS 1

Introduction Grounding is utilized within electrical distribution systems to provide an alternative, low- impedance path around the

DISTRIBUTION BOX

Attach a second grounding wire from the mounting plate (B), to the factory central grounding point. The ground

Equipment Grounding Conductor (EGC) Ground Wire Size Chart

The ground wire that runs with your circuit (the equipment grounding conductor, or EGC) is primarily sized by your

The Basics of Grounding and Bonding

Section 250.4 states the general requirements for grounding and bonding of electrical systems for both grounded and ungrounded

Ground Wire Size Chart NEC 2026

In 2026, NEC Table 250.122 remains the definitive reference for equipment grounding conductor sizing, while Table 250.66 covers

Ground Wire Size Chart

This chart displays the size of a ground conductor for a circuit based on the ampere rating of the circuit protection devices.

National Electrical Code 2023 Basics: Grounding and Bonding Part 1

Learn about the general requirements for grounding and bonding in line with the NEC 2023.

NEC Ground Wire Size Chart: What Size Ground Wire Do You Need

A ground wire size chart that follows will tell you exactly the size of the grounding conductor you need. Now, it''s important to

How to Size Equipment Grounding Conductor (EGC)?

For a proper grounding system, the following step-by-step guide can be used to determine the suitable size of Equipment Grounding

Ground Wire Size Chart

The EGC size chart is based on breaker size, not load, because the ground wire must be thick enough to withstand a

301 Moved Permanently

301 Moved Permanently 301 Moved Permanently cloudflare

D5000 General Electrical Requirements

This Section outlines the requirements for Site Electrical Distribution at the Los Alamos National Laboratory that were applicable at

Grounding and UL 508A Standards

Additional rules for the grounding and bonding of industrial control panels include the sizing

How to Ground an Electrical Panel: A Complete Guide

Learn how to ground an electrical panel step-by-step. Ensure safety, code compliance, and protect your home from

Secondary unit substations design guide

Secondary windings are either full height sheet conductors or wire conductor dependent on the voltage and kVA

Ground Wire Size Chart NEC 2026: Complete Grounding Guide

This comprehensive guide will walk you through everything you need to know about grounding conductor sizing, from

26 05 26 Grounding and Bonding Electrical Systems_06_15_16

For all circuits of systems over 50 volts to ground, include an insulated equipment grounding wire sized according to NEC

Ground Wire Sizing Guide | NEC Grounding Requirements

Size ground wires per NEC requirements. Learn equipment grounding conductor sizes, grounding electrode

Ground Wire Sizing Guide | NEC Grounding Requirements

Learn how to properly size ground wires according to NEC requirements. This comprehensive guide covers

Subpanel Grounding: Answers to Common Questions

subpanel grounding violations. The grounded conductors and the equipment grounds are connected to the same terminal bar,

Grounding Paper

For purposes of grounding calculations, the concentric neutral on older underground residential distribution cables with bare neutral

Size determination, installation method and wiring mode of distribution

The distribution box is the central hub of the home circuit and the general control of our daily power consumption. It is an

Ground Wire Size Chart (NEC 2023): How to Choose the Correct

Ensuring electrical safety in your home begins with proper grounding. This guide, based on the NEC 2023, provides

National grid logo and tag

Customer secondary service wires entering the box pad shall be in accordance with the NEC and shall be approved by the wire

Requirements And Specifications For Installation Of Distribution Boxes

In flammable and explosive environments, explosion-proof distribution boxes should be selected and explosion-proof

UNDERGROUND ELECTRIC DISTRIBUTION CONSTRUCTION

Any borings and sub-surface data including ground water elevations, underground utility and structural locations that may be

NEC Ground Wire Size Chart Explained

NEC ground wire size chart is a crucial resource for electrical engineering and maintenance professionals, providing

GROUND GRID SPECIFICATIONS

PURPOSE AND SCOPE IPMENT, STRUCTURES, ETC. IN ELECTRICAL STATIONS INCLUDING TRANSMISSION AND

Transformer secondary ground wire size

I''m looking for clarity on grounding, especially NEC 250.102 and 250.122 and when/where to use them related to

Related Resources

Ready to Equip Your Data Center?

Request a free quote for 19″ server racks, open frame racks, AI high-density cabinets, intelligent PDUs, environment monitoring, asset tracking, or modular rack systems. EU‑owned German factory – reliable, scalable, and cost‑effective infrastructure for your IT equipment.